CHAPTER 41
Connection cables
405.1200.037.2 - Rel.: 2.21 of 25/02/2008
41-30
ABB PLC
RxD
TxD
CTS
RTS
GND
3
2
5
4
7
25
15
18
TxD
RxD
RTS
CTS
GND
DSR
+12
V
2
3
4
5
9
7
8
10
14
VT side
D-Sub
25 pin male
PLC side
D-Sub
15 pin male
Max. 15 m.
Order code:
CVPLC03102
T200 (KP60)
(RS232)
(See “Chapter 41 -> Connecting the cable shield“)
RxD
TxD
TxD
RxD
2
3
SHD1
3
2
GND GND
PRG
7
6
8 0V
7
25
15
18
CTS
RTS
5
4
RTS
CTS
4
5
VT side
D-Sub
25 pin male
PLC side
D-Sub
9 pin male
Max. 15 m.
Order code:
CVPLC14102
CS31 (KR31 / KT31 / KR91 / KT92 / KT93 / KT94 / KT95)
T200 (KP62)
(RS232)
This note only applies to protocol of CS31 series 90 (non direct).
Once the VT has been connected to and disconnected from the CS31, the PLC
remains in MONITOR mode and the programming software no longer functions
properly. To get the PLC back to normal functioning, use the programming S/W to
access the “PLC commun.2" menu and select the "3 terminal emulation" option
and press the "CTRL" and "W" keys together. At the end the PLC responds by
offering the prompt sign ">".
NOTE ON DIRECT PROTOCOL: You can select the communication speed of
19200 Baud in the PLC by connecting pins #6, #7 and #8 (see fig.). This speed is
handled by CS31 only if the library module CE 19_2COM1is loaded.
NOTE: the cable supplied by ESA does not have the connection represented by
the dotted line.
(See “Chapter 41 -> Connecting the cable shield“)
RxD
TxD
CTS
RTS
GND
TxD
RxD
RTS
CTS
GND
PRG
2
3
4
5
7
6
8 0V
SHD1
3
2
5
4
7
25
15
18
VT side
D-Sub
25 pin male
PLC side
D-Sub
9 pin male
Max. 15 m.
Order code:
CVPLC14202
CS31 (KR31 / KT31)
(RS232)
MODBUS RTU STANDARD PROTOCOL
(See “Chapter 41 -> Connecting the cable shield“)