8. Series 8 I/O Loading
8.6. Setting Priority IOMs
238 Series 8 I/O User's Guide R500
Honeywell April 2017
The following I/O Link Unit table lists the amount of IO Link bandwidth used for both
Priority and normal IOM configuration.
IO Modules
IOM Scan
Rate (mS)
Cycles
Link Units
per Module
Digital Input Modules
Priority
40
43
Digital Input Modules
200
5
8
Digital Input Modules
250
4
7
Digital Input Modules
500
2
5
Digital Input Modules
1000
1
4
Digital Input Modules
2000
0.5
4
Pulse Accumulation
Priority
40
277
Pulse Accumulation
200
5
37
Pulse Accumulation
250
4
30
Pulse Accumulation
500
2
17
Pulse Accumulation
1000
1
10
Pulse Accumulation
2000
0.5
6
Digital Output Modules
Priority
1
4
Digital Output Modules
All
1
4
ANALOG INPUT WITH HART
Priority
20
123
ANALOG INPUT WITH HART
200
5
33
ANALOG INPUT WITH HART
250
4
27
ANALOG INPUT WITH HART
500
2
15
ANALOG INPUT WITH HART
1000
1
9
ANALOG INPUT WITH HART
2000
0.5
6
Analog Input-MUX
200
5
117