8. Series 8 I/O Loading
8.6. Setting Priority IOMs
240 Series 8 I/O User's Guide R500
Honeywell April 2017
IO Modules
IOM Scan
Rate (mS)
Cycles
Link Units
per Module
Digital Output SO Connections
500
2
2
Digital Output SO Connections
1000
1
1
Digital Output SO Connections
2000
0.5
0
Digital Output SO Connections
50
20
18
Digital Output SO Connections
100
10
9
Digital Output SO Connections
200
5
5
Digital Output SO Connections
500
2
2
Digital Output SO Connections
1000
1
1
Digital Output SO Connections
2000
0.5
0
Digital Output PWM
Connections
50
20
46
Digital Output PWM
Connections
100
10
23
Digital Output PWM
Connections
200
5
12
Digital Output PWM
Connections
500
2
5
Digital Output PWM
Connections
1000
1
2
Digital Output PWM
Connections
2000
0.5
1

Table of Contents