EasyManua.ls Logo

Huawei NetCol5000-A025 - WebUI Operations; Preparations and WebUI Login

Huawei NetCol5000-A025
318 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 4-35 Precharging refrigerant when a low-temperature component is
installed
(1) Pressure gauge 1 (2) Pressure gauge 2 (3) Coupling nut (4) Refrigerant steel
cylinder
(5) Electric balance (6) Discharge pipe
needle valve
(7) Liquid pipe needle
valve
(8) Low-pressure
needle valve
Step 5 On the home screen, choose Running > Device Details > Compressor, and view
Suction pressure and Discharge pressure to determine whether they are within
normal ranges. Choose Running > Device Details > EEV, and view the EEV
suction superheat degree to determine whether it is within normal ranges.
Table 4-21 Normal discharge pressure ranges
Ambient
Temperature
Discharge
Pressure Range
Suction pressure
range
Overheating
degree range
< 15°C 1.5–2.5 MPa 0.7–1.2 MPa 8–15°C
15–35°C 1.5–3.1 MPa
35–45°C 2.5–3.8 MPa
> 45°C 3.1–4.15 MPa
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 4 Power-On Commissioning
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 160

Table of Contents

Other manuals for Huawei NetCol5000-A025

Related product manuals