Symptom Possible Cause Measures
Water fails to be injected
to the humidier
cylinder.
1. There is no water
supply or the water
supply is insucient.
2. The water inlet
solenoid valve of the
humidier cylinder is
faulty.
1. Check that the front
water supply valve is
open.
2. Check that the water
inlet solenoid valve is
open when
humidication is
enabled.
If the fault persists, contact Huawei technical support.
6.5 Parts Replacement
After replacing any part, verify that the new part works properly.
6.5.1 Replacing the Air Filter
Prerequisites
● The air
lter needs to be replaced.
● A spare air lter of the same model is available and functional.
Context
Each smart cooling product has two air lters, located in the upper and lower
parts. The air lters need to be maintained from the rear door.
Procedure
Step 1 Open the rear door, rotate the clips on both sides of the upper air lter, and draw
out the upper air
lter, as shown in Figure 6-4.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 6 System Operation and Maintenance