For safe system operation, when smart cooling product components are turned on,
the following coupling relationships are presented:
● When the electric heater is turned on, the indoor fans will turn on
automatically.
● When the electrode
humidier is turned on, the indoor fans and inlet water
solenoid valve will start automatically.
● When the input value of the indoor fan is less than the minimum speed, the
indoor fan will run at the minimum speed.
Step 3 Check that the indoor fans run properly, and no alarm generates.
Step 4 Choose Maint > Diagnostic Mode > Exit or tap to exit the diagnostic mode.
----End
7.1.17 Which Parameters Are Restored to Default Values After
Default Settings Are Operated
After choosing Settings > Restore Defaults >
Comrm, the following parameters
are displayed:
● All parameters displayed on Settings > System Settings.
● All parameters displayed on Settings > Alarm Settings.
● All parameters displayed on Settings > Comm Settings.
● All parameters except for language and time settings displayed on Settings >
Quick Settings.
● Date format and time zone settings displayed on Settings > User Settings.
● All parameters displayed on Maint > Sensor Calibration.
To prevent key data from being lost, you are recommended to record all
parameter values or back up data with export
congurations before restoring
defaults. Then change the parameter values back to the recorded values after
restoring defaults. For details about how to use export
congurations, see 7.1.18
Exporting Data.
After default settings are restored, all communication addresses are changed to 1 and the
communication between all devices and the EMS is disconnected. The communication
addresses must be reset to recover the communication.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 7 FAQ
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 281