Item Requirement Unit
a: When σ
20
is less than 125 µS/cm, the rst vapor exhausting duration of the
humidier is long; when σ
20
greater than 1250 µS/cm, the humidier service life
is
aected.
b: A water softener needs to be installed if the inlet water hardness exceeds 100
mg/L (CaCO
3
).
2.6 Technical Specications
Table 2-8 and Table 2-9 describe the general and optional specications of the
NetCol5000-A.
Table 2-8 General
specications
Item Specications
Cooling mode Air cooled
Refrigerant R410A
Air ow mode Horizontal air ow
Dimensions (H x W x D) ● 2000 mm x 300 mm x 1100 mm (cabinet)
● 2000 mm x 300 mm x 1200 mm (cabinet with
an enclosure frame)
● 2200 mm x 300 mm x 1100 mm (cabinet with
an enclosure frame, customizable)
● 2200 mm x 300 mm x 1200 mm (cabinet with
top and enclosure frames)
Net weight 230 kg
Environmental friendliness REACH, RoHS
● For a smart cooling product with heating and humidication functions, the
general switch is a 40 A, feature C switch that does not derate at 45°C. If the
switch derates largely when the temperature changes, verify that the switch
can work at 40 A for a long time at 45°C.
● For a smart cooling product without heating and
humidication functions, the
general switch is a 32 A, feature C switch that does not derate at 45°C. If the
switch derates largely when the temperature changes, verify that the switch
can work at 25 A for a long time at 45°C.