Figure 6-20 Removing the humidier
Step 8 Install the new humidier and fasteners, install the liquid level detector, connect
the water inlet pipe, and start the humidier.
Step 9 Install the air lter and close the rear door.
Step 10 Power on again, choose Maint > Performance Maint on the home screen to
access the performance maintenance screen, and clear the humidier runtime.
----End
6.5.9 (Optional) Replacing the
Humidier Cylinder
Prerequisites
● The
humidier cylinder needs to be replaced.
● A spare humidier cylinder of the same model is available and functional.
● Tool: at-head screwdriver
Context
The humidier cylinder can be maintained only from the rear.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 6 System Operation and Maintenance
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 248