Tool Name and Appearance
N/A N/A
NO TE
For parts replacement, see the appropriate section for information about the required tools.
6.2.2 Data Record
Before performing monthly maintenance, record data in Table 6-2.
Table 6-2 Recording table
Menu Item Parameter Record
Choose Settings > System Settings
> T/H Sensor.
T/H control type
Temp set point
Humid set point
Choose Common Functions >
Operating Info, or tap Running >
Operating Info.
Current temperature
Current humidity
Rated power voltage
Measured power
voltage
Choose Running > Device Details >
Compressor.
Discharge temp
Discharge pressure
Suction pressure
Tap Teamwork. Teamwork function
Choose Teamwork > Teamwork
Settings.
Total number of units
Number of active
units
6.2.3 Monthly Maintenance
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 6 System Operation and Maintenance
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 178