Temperature
(°C)
Saturation
Pressure-
Surface
Pressure
(MPa)
Temperatur
e (°C)
Saturatio
n
Pressure-
Surface
Pressure
(MPa)
Temperatur
e (°C)
Saturati
on
Pressur
e-
Surface
Pressur
e (MPa)
3 0.78 22 1.43 41 2.39
4 0.81 23 1.47 42 2.45
5 0.84 24 1.51 43 2.51
6 0.87 25 1.56 44 2.57
7 0.9 26 1.60 45 2.63
8 0.93 27 1.65 46 2.7
9 0.96 28 1.69 47 2.76
10 0.99 29 1.74 48 2.83
11 1.02 30 1.79 49 2.9
12 1.05 31 1.84 50 2.97
13 1.09 32 1.89 51 3.04
14 1.12 33 1.94 52 3.11
15 1.16 34 1.99 53 3.19
16 1.19 35 2.04 54 3.26
17 1.23 36 2.1 55 3.34
18 1.27 37 2.15 N/A N/A
3.1.2.2 (Optional) Refrigerant Oil
The recommended refrigerant oil is RL32H/Emkarate. You can purchase it from
Huawei or another vendor. The refrigerant oil purchased from another vendor
should be conrmed by Huawei.
3.1.2.3 (Optional) Oil Trap and Inverted Trap
NO TICE
The operating pressure of the copper pipe, oil trap, and inverted trap should be
greater than 4.5 MPa.