Applicati
on
Scenario
Name Technical Specications Remarks
Indoor
and
outdoor
units
Cord end
terminal for
the cable
between the
indoor and
outdoor units
Bare crimp terminal, single
cord end terminal, 1 mm
2
, 5 A,
tin plating, insertion depth 12
mm, red
Delivered with the
ttings
Cord end
terminal for
the
communicati
ons cable
Common terminal, single cord
end terminal, 0.25 mm
2
, 0.012
m, insertion depth 6 mm, 2 A,
light blue
Delivered with the
ttings
3.1.2.8 (Engineering Procurement) Water Softener
If the water hardness exceeds 100 mg/L (CaCO
3
), install water purication
equipment to reduce scaling and ensure the stable running of the system. The
detailed specications are as follows:
Table 3-9 Water softener specications
Item
Specications
Water ow
0.5 m
3
/h
Water inlet pressure 0.1–0.7 MPa
Water inlet temperature 1–40°C
Water inlet hardness ≤ 800 mg/L
Water outlet hardness ≤ 3 mg/L
Filtration rate 20–25 m/h
Design pressure ≤ 0.6 MPa
Operating pressure 0.2–0.45 MPa
Operating temperature 5–50°C
3.1.3 Deployment Principles
Check cabinets comprehensively and handle problems immediately.
Before installation, check that the environment meets requirements and check
whether reconstruction is needed for routing pipes and cables and
constructing ventilation pipes.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 3 Installation Guide
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 38