Figure 7-17 Setting alarm parameter 2
----End
7.1.16 How to Commission Single Component
Context
● On the diagnostic mode screen, you can turn on or
o components, and
control their output ratio.
● If you need to manually turn on or o system components in diagnostic
mode, ensure that the smart cooling product is started before operation.
● Take commissioning the indoor fan as an example.
Procedure
Step 1 Choose Maint > Diagnostic Mode > Enter.
The screen for entering the diagnostic mode:
● Components are interlocked. Therefore, buttons for turning on or o certain
components are in gray, indicating that operations of the components are not allowed.
● To ensure system security, a component may not promptly respond to operations
performed on this screen. For example, the compressor does not respond promptly after
the
O (On) button is tapped if the shortest running (shutdown) time is not met.
● To exit the diagnostic mode, tap on the status bar.
● The system automatically exits diagnostic mode when it reaches the maximum
diagnostic mode duration.
Step 2 Set Indoor fan to 50%.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 7 FAQ
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 280