Figure 6-29 Removing screws from a high liquid level detector
Step 5 Install the new liquid level detector and connect the interconnection terminal of
the liquid level detector.
Step 6 Tighten screws, connect cables, install the water pan cover, and close the front
door.
----End
6.5.14 (Optional) Replacing the Condenser Pump
Prerequisites
The water pump needs to be replaced.
A spare water pump of the same model is available and functional.
Tools:
at-head screwdriver, socket wrench
Before removing the water pump, drain water from the water pan completely.
Context
The water pump can be maintained only from the front.
Procedure
Step 1 Tap Shutdown on the LCD home screen and turn o the smart cooling product
switch in the PDC.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 6 System Operation and Maintenance