7.1.10 Deleting Logs
Context
Logs can be deleted in a one-click manner.
To delete logs, log in as the admin user.
NO TICE
If you perform this operation, all logs will be deleted, and device maintenance will
be aected. Exercise caution when doing this operation.
Procedure
Step 1 On the home screen, choose Maint > Log Maintenance > Delete Logs > Yes to
delete all the logs.
NO TE
After logs are deleted, the log deletion operation is recorded in the rst log that is
displayed.
----End
7.1.11 Clearing the Runtime
Context
NO TICE
Performance value clearance can be performed only after component
maintenance. Otherwise the component may run overtime and degrade
performance.
Procedure
Step 1 On the home screen, choose Maint > Performance Maint.
Step 2 Tap Clear of a
specic performance parameter to clear its runtime.
----End
7.1.12 Calibrating a Sensor
Context
Calibrate a sensor if the displayed temperature or humidity on the sensor deviates
from the actual value. For example, if the return air temperature measured by
other temperature detection devices at the return air detection point is 20°C while
the value measured by the sensor is 22°C, the sensor has an error of 2°C, and the
calibration value should be set to –2°C.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 7 FAQ
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 274