EasyManua.ls Logo

Huawei NetCol5000-A025 - Page 199

Huawei NetCol5000-A025
318 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Al
ar
m
ID
Alarm
Name
Ala
rm
Sev
erit
y
Impact Possible Causes Solution
a0
4
6
Compre
ssor
antifree
ze
protecti
on
alarm
CRI
TIC
AL
Generates
an alarm
and shuts
down the
smart
cooling
product.
1. The refrigerant
leaks.
2. The pressure
displayed is
dierent from
the actual
pressure.
3. The
lter dryer
is blocked.
4. The expansion
valve is blocked
or stuck, or the
expansion valve
coil and cable
connections are
faulty.
5. The indoor fan is
faulty.
6. The ambient
temperature is
below the lower
threshold.
1. Identify and repair
the leaking point,
and rell
refrigerant after
maintenance.
2. Calibrate or replace
the pressure sensor.
3. Maintain or replace
the
lter dryer.
4. Maintain or replace
the expansion
valve or the coil,
and reconnect
cables.
5. Maintain or replace
the indoor fan.
6. Measure the
ambient
temperature.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 6 System Operation and Maintenance
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 189

Table of Contents