EasyManua.ls Logo

Huawei NetCol5000-A025 - Page 214

Huawei NetCol5000-A025
318 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Al
ar
m
ID
Alarm
Name
Ala
rm
Sev
erit
y
Impact Possible Causes Solution
a1
9
1
EEV
drive
power
failure
alarm
CRI
TIC
AL
Generates
an alarm
and shuts
down the
compressor.
The main control
module is faulty.
Replace the main
control module.
a1
9
3
Air-side
di
pressur
e
sensor
fault
MA
JOR
Generates
an alarm.
1. The dierential
pressure sensor
cable is loose or
damaged.
2. The pressure
tube of the
dierential
pressure sensor
is reversely
connected.
3. The
dierential
pressure sensor
is faulty.
1. Check the cable
connection to the
dierential
pressure sensor.
2. Check the tube
connection to the
dierential
pressure sensor.
3. Maintain or replace
the
dierential
pressure sensor.
a2
2
0
Wizard
startup
is in
progres
s
WA
RNI
NG
Generates
an alarm.
Wizard startup is in
progress.
Wait until wizard
startup is complete or
clear the Wizard
startup in progress
alarm manually to
exit wizard startup.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 6 System Operation and Maintenance
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 204

Table of Contents