Impact Possible Causes Solution
a2
7
2
Teamw
ork
networ
king
abnorm
al
alarm
WA
RNI
NG
Generates
an alarm
and exits
from
teamwork
mode to
work in
standalone
mode.
1. Any two smart
cooling product
units have the
same address.
2. The software
versions of the
smart cooling
products in the
group are
inconsistent.
3. The sensor that
corresponds to
the temperature
and humidity
control type for
the master unit
is not enabled
on this smart
cooling product.
1. Change the
addresses of the
smart cooling
product units.
2. Upgrade the smart
cooling product
software by
referring to the
section that
describes the
mapping between
the software and
the teamwork
versions in the
upgrade guide.
3. Enable the sensor
that corresponds to
the temperature
and humidity
control type for the
master unit on this
smart cooling
product.
Teamw
ork
networ
king
abnorm
al
alarm
WA
RNI
NG
Generates
an alarm
and exits
from
teamwork
mode to
work in
standalone
mode.
1. Teamwork
settings are
incorrect for
slave units.
2. The number of
smart cooling
product units is
incorrectly set
on the master
unit.
3. A slave unit is
oine.
1. Modify teamwork
settings for slave
units to enable
slave units to join
the teamwork
group.
2. Set the total
number of units on
the master unit to
the actual number
of units.
3. Check the
teamwork cable
connection and
running status of
the slave units.
NetCol5000-A025 In-row Air Cooled Smart Cooling
Product
User Manual (300 mm Width) 6 System Operation and Maintenance
Issue 15 (2020-12-10) Copyright © Huawei Technologies Co., Ltd. 206