5 CANopen communication
5.20 Index table
203
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
1 COB-ID used by
TxPDO 5
1664 +
NID
385 {1} 2047
Definition of specific identifiers for
process data object 5 (NID= Node
ID / node address)
2 Transmission type
255 0 {1} 255
Defining the transmission mode
0 Function deactivated
The output data are accepted on
sync telegram transmission.
1 ... 240 Process data transfer after sync no. 1
...
Process data transfer according to
sync no. 240
The output data is accepted after
the set number of sync telegrams
(1 ... 240) has been transmitted
254 Time-controlled process data
transfer
Only if a cycle time is set in I-180x,
subindex 5
255 Event-controlled process data
transfer
255 Event-controlled process data
transfer with cyclic overlay
Only if a cycle time is set in I-180x,
subindex 5
3 Inhibit time
0 0 {1 ms} 65535
Blocking time
5Event time
0 0 {1 ms} 65535
Cycle time
I-1805
1 COB-ID used by
TxPDO 6
448 +
NID
385 {1} 2047
Definition of specific identifiers for
process data object 6 (NID= Node
ID / node address)
2 Transmission type
255 0 {1} 255
Defining the transmission mode
0 Function deactivated
The output data are accepted on
sync telegram transmission.
1 ... 240 Process data transfer after sync no. 1
...
Process data transfer according to
sync no. 240
The output data is accepted after
the set number of sync telegrams
(1 ... 240) has been transmitted
254 Time-controlled process data
transfer
Only if a cycle time is set in I-180x,
subindex 5
255 Event-controlled process data
transfer
255 Event-controlled process data
transfer with cyclic overlay
Only if a cycle time is set in I-180x,
subindex 5
3 Inhibit time
0 0 {1 ms} 65535
Blocking time
5Event time
0 0 {1 ms} 65535
Cycle time
I-1806
Index Name Possible settings Info