Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 214
5 CANopen communication
5.20 Index table
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
I-6424
Upper limit analog
input
0x00000000 {1} 0xFFFFFFFF
1 Channel 1
0
2 Channel 2
0
... ...
...
36 Channel 36
0
I-6425
Lower limit analog
input
0x00000000 {1} 0xFFFFFFFF
1 Channel 1
0
2 Channel 2
0
... ...
...
36 Channel 36
0
I-6426
Delta limit analog
input
0x00000000 {1} 0xFFFFFFFF
1 Channel 1
0
2 Channel 2
0
... ...
...
36 Channel 36
0
I-6443
Error mode analog
output
0 {1} 255
Configures analog output
monitoring
I-6443 0
All analog outputs retain the last
value output
255
Response from I-6444
In I-6444, the response can be
configured individually for each
analog output
1 Channel 1
0
2 Channel 2
0
... ...
...
36 Channel 36
0
I-6444
Error value analog
output
-32768 {1} 32767
Configures the individual analog
output responses
The analog outputs provide the set
value
1 Channel 1
0
2 Channel 2
0
... ...
...
36 Channel 36
0
Index Name Possible settings Info
Lenze Selection