Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17 344
7 EtherCAT communication
7.6 Parameterising temperature measurement
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
08 Conversion time
channel 1
You can set the transformer speed as a function of the
interference frequency suppression (see 0x3105/x) for each
channel.
0 (0x00): At 50 Hz: 324.1 ms/channel 16 bits; at 60 Hz: 270.5 ms/
channel 16 bits
1 (0x01): at 50 Hz: 164.2 ms/channel 16 bits;
at 60 Hz: 137.2 ms/channel 16 bits
2 (0x02): At 50 Hz: 84.2 ms/channel 16 bits;
at 60 Hz: 70.5 ms/channel 16 bits
3 (0x03): At 50 Hz: 44.1 ms/channel 16 bits;
at 60 Hz: 37.2 ms/channel 16 bits
4 (0x04): At 50 Hz: 24.2 ms/channel 16 bits;
at 60 Hz: 20.5 ms/channel 16 bits
5 (0x05): At 50 Hz: 14.2 ms/channel 16 bits;
at 60 Hz: 12.2 ms/channel 16 bits
6 (0x06): At 50 Hz: 9.2 ms/channel 16 bits;
at 60 Hz: 8.0 ms/channel 16 bits
7 (0x07): At 50 Hz: 6.6 ms/channel 15 bits;
at 60 Hz: 5.9 ms/channel 15 bits
8 (0x08): At 50 Hz: 4.2 ms/channel 13 bits;
at 60 Hz: 3.8 ms/channel 13 bits
0x00
09 Upper limit value
channel 1
You can define an upper or lower limit value for each channel. For
this you can only specify values from the nominal range,
otherwise you'll receive a parameterisation error. By
specification of 0x7FFF for the upper or 0x8000 for the lower
limit value, the corresponding limit value is deactivated.
If your measured value is outside a limit value and you have
activated the limit value monitoring, a process alarm is
triggered.
0x7FFF
0A Lower limit value
channel 1
0x8000
Channel 2
0B Function channel 2 See channel 1 0x50
0C Conversion time
channel 2
See channel 1 0x00
0D Upper limit value
channel 2
See channel 1 0x7FFF
0E Lower limit value
channel 2
0x8000
Channel 3 (for two-wire conductor connections only)
0F Function channel 3 See channel 1 0x50
10 Conversion time
channel 3
See channel 1 0x00
11 Upper limit value
channel 3
See channel 1 0x7FFF
12 Lower limit value
channel 3
0x8000
Channel 4 (for two-wire conductor connections only)
13 Function channel 4 See channel 1 0x50
14 Conversion time
channel 4
See channel 1 0x00
15 Upper limit value
channel 4
See channel 1 0x7FFF
16 Lower limit value
channel 4
0x8000
Subindex Name Description/value Lenze