7 EtherCAT communication
7.6 Parameterising temperature measurement
345
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Measuring range
Measuring range Measured value Signal range Range
(Fct. no.)
2-wire: PT100
(0x50)
+1000 °C +10000 Overflow
-200 ... +850 °C -2000 ... +8500 Nominal range
-243 °C -2430 Underflow
2-wire: PT1000
(0x51)
+1000 °C +10000 Overflow
-200 ... +850 °C -2000 ... +8500 Nominal range
-243 °C -2430 Underflow
2-wire: NI100
(0x52)
+295 °C +2950 Overflow
-60 ... +250 °C -600 ... +2500 Nominal range
-105 °C -1050 Underflow
2-wire: NI1000
(0x53)
+295 °C +2950 Overflow
-60 ... +250 °C -600 ... +2500 Nominal range
-105 °C -1050 Underflow
3-wire: PT100
(0x58)
+1000 °C +10000 Overflow
-200 ... +850 °C -2000 ... +8500 Nominal range
-243 °C -2430 Underflow
3-wire: PT1000
(0x59)
+1000 °C +10000 Overflow
-200 ... +850 °C -2000 ... +8500 Nominal range
-243 °C -2430 Underflow
3-wire: NI100
(0x5A)
+295 °C +2950 Overflow
-60 ... +250 °C -600 ... +2500 Nominal range
-105 °C -1050 Underflow
3-wire: NI1000
(0x5B)
+295 °C +2950 Overflow
-60 ... +250 °C -600 ... +2500 Nominal range
-105 °C -1050 Underflow
4-wire: PT100
(0x60)
+1000 °C +10000 Overflow
-200 ... +850 °C -2000 ... +8500 Nominal range
-243 °C -2430 Underflow
4-wire: PT1000
(0x61)
+1000 °C +10000 Overflow
-200 ... +850 °C -2000 ... +8500 Nominal range
-243 °C -2430 Underflow
4-wire: NI100
(0x62)
+295 °C +2950 Overflow
-60 ... +250 °C -600 ... +2500 Nominal range
-105 °C -1050 Underflow
4-wire: NI1000
(0x63)
+295 °C +2950 Overflow
-60 ... +250 °C -600 ... +2500 Nominal range
-105 °C -1050 Underflow
2-wire: 0 ... 60
(0x70)
--Overflow
0 ... 60 0 ... 32767 Nominal range
--Underflow
2-wire: 0 ... 600
(0x71)
--Overflow
0 ... 600 0 ... 32767 Nominal range
--Underflow