8 DeviceNet communication
8.5 Parameterising the counter
435
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Parameter data
Position in
string
Name Description/value Lenze
No.
1 Diagnostics A diagnostic alarm occurs if the same event triggers a further
process alarm during a process alarm processing.
Bit 5 ... 0: Reserved
Bit 6: Diagnostic alarm(0 = inhibited; 1 = enabled)
Bit 7: Reserved
0x00
2 Input frequency
Track A
Filters for instance serve to filter signal peaks in the case of
an unclean input signal.
0 (0x00): 500 kHz
1 (0x01): 300 kHz
2 (0x02): 100 kHz
3 (0x03): 60 kHz
4 (0x04): 30 kHz
6 (0x06): 10 kHz
7 (0x07): 5 kHz
8 (0x08): 2 kHz
9 (0x09): 1 kHz
Other values are not permissible!
0x02
3 Input frequency
Track B
0x02
4 Input frequency
Latch
0x02
5 Input frequency
Gate
0x02
6 Input frequency
Reset
0x00
7 Reserved
8 Alarm response Setting activates process alarm
Bit 0: Proc. alarm HW gate open
Bit 1: Proc. alarm HW gate closed
Bit 2: Proc. alarm overflow
Bit 3: Proc. alarm underflow
Bit 4: Proc. alarm comparison value
Bit 5: Proc. alarm final value
Bit 6: Proc. alarm latch value
Bit 7: Reserved
0x80
9 Numerator function Bit 5 ... 0:
0b0000000 = continuous counting
0b000001 = single counting, main counting direction is
forward
0b000010 = single counting, main counting direction is
backward
0b000100 = single counting, no main counting direction
0b001000 = periodic counting, main counting direction is
forward
0b010000 = periodic counting, main counting direction is
backward
0b100000 = periodic counting, no main counting direction
Bit 7 ... 6: Reserved
0x40