9 PROFINET communication
9.8 Parameterising the counter
521
Lenze · I/O system 1000 · Reference Manual · DMS 5.0 EN · 09/2016 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Read data: 12 bytes
Count value: Current counter content
Write data: 12 bytes
Comparison value: With the comparison value you can specify a value which, by comparison with
the current counter content, can impact the counter output or trigger a process alarm. The response
of the comparison bit STS_COMP in the counter status or the process alarm is to be specified via data
record 0x80 for counter 1 and 0x82 for counter 2.
Counter modules EPM-S600 ... EPM-S603 – control and status words
( 27)
Input area in the process image
Addr. Access Assignment
+0 Double word Counter 1: count value
+4 Double word Counter 2: count value
+8 Word Counter 1: Status word
+10 Word Counter 2: Status word
Output area in the process image
Addr. Access Assignment
+0 Double word Counter 1: Comparison value
+4 Double word Counter 2: Comparison value
+8 Word Counter 1: Control word
+10 Word Counter 2: Control word