Address Name / seng range / [default seng] Informaon
54 Quick stop acve TRUE if quick stop is acve. Otherwise FALSE.
55 Inverter disabled (safety) TRUE if the integrated safety system has inhibited the inverter.
Other
wise FALSE.
Not available
56 Fault acve TRUE if error is acve. Otherwise FALSE.
57 Error (non-reseable) acve TRUE if non-reseable error is acve. Otherwise FALSE.
58 Device warning acve TRUE if warning is acve. Otherwise FALSE.
•
A warning has no impact on the operang status of the inverter.
•
A warning is reset automacally if the cause has been eliminated.
59 Device trouble acve TRUE if a fault is acve. Otherwise FALSE.
•
In the event of a fault, the motor is brought to a standsll with the
quick stop ramp. The inverter is then disabled.
•
Excepon: In case of a serious fault, the inverter is disabled
immediately. The motor has no torque (coasts).
•
The error state will be le automacally if the error condion is not
acve anymore.
•
The r
estart behaviour
aer trouble can be congured. 4Automac
restart aer a fault^ 226
60 Heatsink temperature warning acve TRUE if current heatsink temperature > warning threshold for
temperature monitoring. Otherwise FALSE.
•
Display of the current heatsink temperature in 0x2D84:001 (P117.01).
•
Seng of the warning threshold in 0x2D84:002.
66 Flying restart circuit acve TRUE if ying restart circuit acve is acve. Otherwise FALSE.
4Flying restart circuit^ 154
67 DC braking acve TRUE if DC braking is acve. Otherwise FALSE.
4DC br
aking^ 158
68 Stop command acve TRUE if delay to standsll acve. Otherwise FALSE.
69 Rotaonal
direcon reversed TRUE if output frequency is negave. Otherwise FALSE.
70 Frequency threshold exceeded TRUE if current output frequency > frequency threshold. Otherwise
FALSE.
•
Display of the current output frequency in 0x2DDD (P100.00).
•
Seng Frequency threshold in 0x4005 (P412.00).
4Trigger acon if a frequency threshold is exceeded^ 242
71 Actual speed = 0
TRUE if current output frequency = 0 Hz (± 0.01 Hz),
irrespecve of the
operang mode. Otherwise FALSE.
•
Display of the current output frequency in 0x2DDD (P100.00).
72 Setpoint speed reached TRUE if frequency setpoint reached. Otherwise FALSE.
73 PID feedback = setpoint TRUE if the controlled feedback variable = process controller setpoint (±
in 0x404D:003
(P608.03) set hysteresis). Otherwise FALSE.
4Conguring the process controller^ 98
74 PID sleep mode acve TRUE if the inverter is in "PID sleep mode". Otherwise FALSE.
4Pr
ocess controller sleep mode^ 105
75 PID MIN alarm acve TRUE if feedback variable (with acvated PID control) < MIN alarm
thr
eshold. Otherwise FALSE.
•
Seng of MIN alarm threshold in 0x404D:001 (P608.01).
4
Conguring the process controller^ 98
76 PID MAX alarm acve TRUE if the feedback variable (with acvated PID control) > MAX alarm
threshold. Otherwise FALSE.
•
Seng of MAX alarm threshold in 0x404D:002 (P608.02).
4
Conguring the process controller^ 98
77 PID MIN-MAX alarm acve TRUE if no PID alarm is acve with acvated PID control (MIN alarm
threshold < feedback variable < MAX alarm threshold). Otherwise FALSE.
•
Seng of MIN alarm threshold in 0x404D:001 (P608.01).
•
Seng of MAX alarm threshold in 0x404D:002 (P608.02).
4
Conguring the process controller^ 98
78 Current limit reached
TRUE if current motor current ≥ ma
ximum current. Otherwise FALSE.
•
Display of the present motor current in 0x2D88 (P104.00).
•
Seng for the maximum current in 0x6073 (P324.00).
I/O extensions and control connecons
Congure digital outputs
R
elay output
212