Address Name / seng range / [default seng] Informaon
0x2839:006 Fault conguraon: Fault handling in case of state
chang
e
Selecon whether a pending error is to be reset via the funcons
"Enable inverter" 0x2631:001 (P400.01) and "Run" 0x2631:002
(P400.02) as well.
0 Reset fault
1 Do not reset fault
Example for operang mode
•
S
witch S1 starts the motor in forward direcon of rotaon.
De-asserng Switch S1 stops
the motor again.
•
Switch S2 resets the current error if the error condion is not acve anymore and the error
is reseable.
Connecon plan Funcon
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
X3
S1 S2 S3 S4
1k ...10k
0 ... 10 V
R1
Potenometer R1 Frequency setpoint selecon
Switch S1 Run
Switch S2 Reset fault
Switch S3 -
Switch S4 -
Parameter Designaon Seng for this example
0x2631:001 (P400.01) Enable inverter Constant TRUE [1]
0x2631:002 (P400.02) Run Digital input 1 [11]
0x2631:004 (P400.04) Reset fault Digital input 2 [12]
0x2631:013 (P400.13) Reverse rotaonal direcon Not connected [0]
0x2631:018 (P400.18) Acvate preset (bit 0) Not connected [0]
0x2824 (P200.00) Control selecon Flexible I/O conguraon [0]
0x2838:003 (P203.03) Stop method Standard ramp [1]
0x2860:001 (P201.01) Frequency control: Default setpoint source Analog input 1 [2]
0x2918 (P221.00) Deceleraon
me 1 5.0 s
0x291C (P225.00) Quick stop deceleraon me 1.0 s
Diagnoscs and fault eliminaon
Error handling
Err
or reset