Address Name / seng range / [default seng] Informaon
0x2631:031
(P400.31)
Funcon list: Start sequence
(Funcon list: Seq: Start)
Seng can only be changed if the inverter is
disabled.
Fr
om version 03.00
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the "Start sequence" funcon.
Trigger = FALSE↗TRUE (edge): Start selected sequence.
T
rigger = TRUE↘FALSE (edge): No acon.
Notes:
Aer the start, the sequencer remains acvated unl the funcon
"Stop sequence" 0x2631:035 (P400.35) or the funcon "Abort
sequence" 0x2631:036 (P400.36) is executed. A normal stop
command does not reset the start command for the sequencer.
For a status-controlled start, the funcon "Run/abort sequence"
0x2631:030 (P400.30) is oponally available.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:032
(P400.32)
Funcon list: Next sequence step
(Funcon list: Seq: Next step)
Seng can only be changed if the inverter is
disabled.
From version 03.00
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the "Next sequence step" funcon.
Trigger = FALSE↗TRUE (edge): Next sequence step.
T
rigger = TRUE↘FALSE (edge): No acon.
Notes:
The execuon of the current step is completed even if the me
parameterised for the segment has not elapsed yet.
The funcon is only relevant for Sequencer mode 0x4025 (P800.00) =
"Step operaon [2]" or "Time & step operaon [3]".
A jump to the next sequence step is not possible if the sequence
pauses, the sequence is suspended or the nal segment is executed.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:033
(P400.33)
Funcon list: Pause sequence
(Funcon list: Seq: Pause)
Seng can only be changed if the inverter is
disabled.
From version 03.00
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the "Pause sequence" funcon.
Trigger = TRUE: Pause sequence.
T
rigger = FALSE: Connue sequence.
Notes:
During the pause, the sequence stops in the current step. The
expiraon of the me set for the segment is stopped.
The sequencer setpoint connues to remain acve.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:034
(P400.34)
Funcon list: Suspend sequence
(Funcon list: Seq: Suspense)
Seng can only be changed if the inverter is
disabled.
From version 03.00
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the "Suspend sequence" funcon.
Trigger = TRUE: Suspend sequence.
T
rigger = FALSE: Connue sequence.
Notes:
This funcon serves to temporarily change over to the standard
setpoint or the setpoint source selected via setpoint change-over.
The sequence is connued at the point where it was suspended.
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:035
(P400.35)
Funcon list: Stop sequence
(Funcon list: Seq: Stop)
Seng can only be changed if the inverter is
disabled.
From version 03.00
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the "Stop sequence" funcon.
Trigger = FALSE↗TRUE (edge): Stop sequence.
T
rigger = TRUE↘FALSE (edge): No acon.
Notes:
If the sequence is stopped, it is jumped to the nal segment.
The further execuon depends on the selected End of sequence
mode 0x402F (P824.00).
0 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:036
(P400.36)
Funcon list: Abort sequence
(Funcon list: Seq: Abort)
Seng can only be changed if the inverter is
disabled.
Fr
om version 03.00
Further possible sengs: 4T
rigger list ^ 52
Assignment of a trigger for the "Abort sequence" funcon.
Trigger = FALSE↗TRUE (edge): Abort sequence.
T
rigger = TRUE↘FALSE (edge): No acon.
Notes:
This funcon serves to directly stop the sequence without the nal
segment being executed. In this case, the standard setpoint or the
setpoint source selected via setpoint change-over is acve again.
0 Not connected No trigger assigned (trigger is constantly FALSE).
Conguring the frequency control
Congure setpoint sources
Sequencer
93