Gocator Line Profile Sensors: User Manual
Specifications 505
Serial Output
Serial RS-485 output is connected to Serial_out as shown below.
Function Pins
Serial_out B, C
Analog Output
The Sensor I/O Connector defines one analog output interface: Analog_out.
Function Pins Current Range
Analog_out P, F 4 20 mA
Current Mode Voltage Mode
To configure for voltage output, connect a 500 Ohm ¼ Watt resistor between Analog_out+ and Analog_
out- and measure the voltage across the resistor. To reduce the noise in the output, we recommend
using an RC filter as shown below.