7 Operation
Maschinenfabrik Reinhausen GmbH 2019156 5163667/06 ENETOS
®
IM
Figure108: Setting power flow monitoring
To set power flow monitoring, proceed as follows:
1. Go to Settings > Parameters > Power flow monitoring.
2. Select the desired parameter.
3. Set parameter.
4. Press the Accept button to save the modified parameter.
Setting the hysteresis
You can use this parameter to set the hysteresis. You can use this to avoid
the unnecessary generation of messages if the measured value fluctuates
around a threshold value.
Setting the delay time
You can use this parameter to set the delay time in order to delay the issuing
of the Reversal of power flow message.
Setting the behavior
You can use this parameter to set the behavior in the event of a reversal of
power flow. You can select the following options:
Setting Behavior
Off The negative power flow is ignored.
Automatic regulation remains active.
Event only The Reversal of power flow event is issued.
If Z compensation is activated, this function is deacti-
vated.
Automatic regulation remains active.