7 Operation
Maschinenfabrik Reinhausen GmbH 2019162 5163667/06 ENETOS
®
IM
∆U-3ph/∆φ-3ph behavior
You can use this parameter to set the behavior of the device when the event
message is issued. You can select the following options:
Setting Behavior
Off The limit value is not monitored.
Auto blocking ▪ An event message is issued.
▪ Automatic regulation is blocked.
Auto/manual blocking ▪ An event message is issued.
▪ Automatic regulation is blocked.
▪ You cannot perform tap-change operations in manual
mode.
Table51: Behavior when an event message is issued
7.8.8 Temperature monitoring
You can set different limit values for every measured/calculated temperature
. If the measured temperature is greater than limit value > or >>, the device
triggers an event message. If the measured temperature is less than limit
value < or <<, the device triggers an event message.
Figure111: Temperature monitoring
To set the temperature monitoring, proceed as follows:
1. Go to Settings > Parameters > Temperature monitoring.
2. Select the parameter you want.
3. Set the parameter you want.
4. Press the Accept button to save the modified parameter.