7 Operation
Maschinenfabrik Reinhausen GmbH 2019158 5163667/06 ENETOS
®
IM
Behavior limit value
You can use this parameter to set the behavior of the device when the event
message is issued. You can select the following options:
Setting Behavior
Off Tap position monitoring is disabled.
Auto blocking po-
sition+
The automatic control does not perform a tap-change operation
in the direction of a higher tap position (position+).
You can still perform a tap-change operation in the direction of
a higher tap position (position+) in manual mode.
Auto blocking po-
sition-
The automatic control does not perform a tap-change operation
in the direction of a lower tap position (position-).
You can still perform a tap-change operation in the direction of
a lower tap position (position-) in manual mode.
Auto/manual
blocking position+
The automatic control does not perform a tap-change operation
in the direction of a higher tap position (position+).
You cannot perform a tap-change operation in the direction of a
higher tap position (position+) in manual mode.
Auto/manual
blocking position-
The automatic control does not perform a tap-change operation
in the direction of a lower tap position (position-).
You cannot perform a tap-change operation in the direction of a
lower tap position (position-) in manual mode.
Operations counter
The device's operations counter is automatically increased with every tap-
change operation. You can use this parameter to set the number of tap-
change operations, such as for a comparison with the operations counter of
the motor-drive unit.
To set tap position monitoring, proceed as follows:
1. Go to Settings > Parameters > Tap position monitoring.
2. Select the parameter you want.
3. Set parameter.
4. Press the Accept button to save the modified parameter.
Also refer to
2 Tap position monitoring (optional) [157]
7.8.6 Bandwidth monitoring
The following limit values are monitored via bandwidth monitoring. The set
bandwidth [Section 7.3.2, Page 111] is used for this purpose.
Upper bandwidth
Lower bandwidth