EasyManua.ls Logo

MR ETOS IM - Page 231

MR ETOS IM
412 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Operation
Maschinenfabrik Reinhausen GmbH 2019 2315163667/06 EN ETOS
®
IM
If you have connected sensors over the MR sensor bus, you must select the
"Modbus" signal type for the desired functions. Observe the additional infor-
mation provided in the MR sensor bus [Section 7.16, Page 219] section.
NOTICE
Damage to the device and sensors!
Incorrectly connected and configured analog inputs/outputs may result in
damage to the device and sensor.
Follow information about connecting analog sensors.
Configure analog inputs and outputs according to the connected sensors.
The following information is displayed in tabular form for configuring the ana-
log inputs and outputs. Grayed out elements cannot be changed.
Property Options
Function Function of the analog input (I: ...) or the analog output (O: ...). You
can adjust the designation.
Card/channel
1)
Select the slot and channel of the analog sensor. Note the connec-
tion diagram supplied.
Signal type Select signal type of analog sensor or deactivate analog output.
4...20mA
PT100-2/3/4, PT1000-2/3/4
Modbus (MR sensor bus)
Min/Max
1)
Set the minimum and maximum values of the sensor, e.g. with a
4...20 mA signal, the corresponding measured value for 4 mA and
the corresponding value for 20 mA.
Table60: Configuration of the analog inputs and outputs
1)
Not available with sensors connected over the MR sensor bus (Modbus).
Figure177: Configuring analog inputs/outputs

Table of Contents

Related product manuals