7 Operation
Maschinenfabrik Reinhausen GmbH 2019272 5163667/06 ENETOS
®
IM
Baud rate (only with Modbus-RTU and Modbus-ASCII)
You can use this parameter to set the serial interface's baud rate. You can
select the following options:
9600 baud
19200 baud
38400 baud
57600 baud
115200 baud
To select the baud rate, proceed as follows:
1. Go to Settings > Parameters > Modbus > Baud rate.
2. Select baud rate.
3. Press the Accept button to save the modified parameter.
Number of databits (only with Modbus-RTU and Modbus-ASCII)
You can use this parameter to set the number of databits.
To set the number of databits, proceed as follows:
1. Go to Settings > Parameters > Modbus > Number of databits.
2. Set number of databits.
3. Press the Accept button to save the modified parameter.
Parity (only with Modbus-RTU and Modbus-ASCII)
You can use this parameter to set the parity. You can select the following
options:
None
Even
Odd
To set the parity, proceed as follows:
1. Go to Settings > Parameters > Modbus > Parity.
2. Select parity.
3. Press the Accept button to save the modified parameter.
Number of stop bits (only with Modbus-RTU and Modbus-ASCII)
You can use this parameter to set the number of stop bits.
To set the number of stop bits, proceed as follows:
1. Go to Settings > Parameters > Modbus > Number of stop bits.
2. Set number of stop bits.
3. Press the Accept button to save the modified parameter.