4 Product description
Maschinenfabrik Reinhausen GmbH 201928 5163667/06 ENETOS
®
IM
Status of the motor-drive unit (motor protective switch, motor is running)
Optional: Motor Current Index
Automatic voltage regulation AVR basic
Measurement of voltage and current
1 desired value
Voltage regulation with linear delay time T1
Status of the motor-drive unit (motor protective switch, motor is running)
Automatic voltage regulation AVR pro
Measurement of voltage and current
Desired value in accordance with order (1, 3 or 5 desired values,
TDSC, analog desired value specification, gradual desired value speci-
fication, desired value using BCD)
Automatic voltage regulation with linear or integral delay time T1 and
with delay time T2
Parallel operation
Line drop compensation
Status of the motor-drive unit (motor protective switch, motor is running)
Bandwidth monitoring
Function monitoring
Limit value monitoring (voltage, current, power, phase angle)
Cooling system control
2, 4 or 6 cooling stages, can be individually parameterized
Load-dependent mode (for early activation of cooling stages)
Periodic mode (for regular activation of cooling stages)
Alternating mode (for equal loading of similar cooling stages)
Cooling stage monitoring (2, 4 or 6 cooling stages)
DGA
Up to 10 gases
Relative moisture in oil
Monitoring of the absolute values and rates of increase
Optional: Rogers, Duval, Dörnenburg and IEC 60599 analyses
MR sensor bus
Calculation of the transformer overload capability (emergency operation)
Bushing monitoring
Monitoring of oil-impregnated paper bushings (OIP) and resin-impreg-
nated paper bushings (RIP) at voltage levels of U
m
= 123...420kV (with
voltage levels up to 765kV on request)
Optional: Monitoring of 6 bushings, where 3 bushings each form one
set (field 1 and field 2)
Online monitoring of the bushing by means of capacitance measure-
ment and dissipation factor measurement