9 Messages
Maschinenfabrik Reinhausen GmbH 2019338 5163667/06 ENETOS
®
IM
No. Name Description Remedy Q
1
42 CAN bus address The CAN bus address is already
being used for another
TAPCON®.
Make sure that different CAN bus
addresses are configured for
each TAPCON®. Use a different
CAN bus address.
-
43 Invalid tap position: Follower The tap position of a follower in
parallel operation is invalid.
Check the function and wiring of
the follower's tap position capture.
Connect as per connection dia-
gram.
-
44 Invalid tap position: Master The tap position of a master in
parallel operation is invalid.
Check the function and wiring of
the master's tap position capture.
Connect as per connection dia-
gram.
-
45 Blocking activated Blocking has been activated by
another TAPCON®.
Check the current operating con-
ditions of the transformers in par-
allel operation and the set param-
eters for the corresponding
TAPCON®.
-
46 Invalid measured current
value in parallel operation
group
The received measured current
value of another TAPCON® in
parallel operation is invalid.
Current measurement of the af-
fected TAPCON® is not working
correctly. Check the measure-
ment transformer and the wiring
of the corresponding TAPCON®.
-
47 Invalid measured voltage
value in parallel operation
group
The received measured voltage
value of another TAPCON® in
parallel operation is invalid.
The voltage-measurement system
of the affected TAPCON® is not
working properly. Check the mea-
surement transformer and the
wiring of the corresponding
TAPCON®.
-
48 No other TAPCON® in paral-
lel operation group
There are no other TAPCON®
units involved in parallel opera-
tion.
Check the current operating con-
ditions of the transformers in par-
allel operation as well as the op-
erational readiness and correct
wiring of the TAPCON® units in-
volved in parallel operation.
-
49 CAN bus node is missing No CAN bus communication with
other TAPCON® units present.
CAN bus communication not cor-
rectly configured. Check wiring as
per connection diagram. Use
CAN bus address ≠0. Assign a
separate CAN bus address to
each TAPCON®.
-
50 Motor runtime exceeded The motor runtime has been ex-
ceeded.
Check the functional readiness of
the motor-drive unit and the set
parameters. Ensure that the value
of the set motor runtime matches
the affected motor-drive unit.
-
51 Invalid tap position The captured tap position is in-
valid.
Check the function and wiring of
tap position capture of the corre-
sponding TAPCON®. Connect as
per connection diagram.
-
52 Generic event 1 Generic event 1 Generic event 1 -