9 Messages
Maschinenfabrik Reinhausen GmbH 2019 3435163667/06 EN ETOS
®
IM
No. Name Description Remedy Q
1
260 Limit value ∆U-3ph The limit value for the difference
in voltage between the three
phases has been exceeded.
Check the current operating con-
ditions of the transformer and the
set parameter ∆U-3ph.
-
263 Limit value ∆φ-3ph The limit value for the angle dif-
ference between the three
phases is exceeded.
Check the current operating con-
ditions of the transformer and the
set parameter ∆φ-3ph.
-
266 Test tap or configuration faulty The connection and/or configura-
tion of the three-phase measure-
ment is faulty.
Inspect the connection of the cur-
rent transformer and voltage
transformer and the configuration
of the three-phase measurement.
-
267 cosφ interpolation active The parallel operation is carried
out with interpolated values.
No CAN bus communication with
other TAPCON® units present.
Check wiring as per connection
diagram.
-
272 Limit value ∆φ< Value has fallen below the limit
value for phase angle difference
∆φ<.
Check the current operating con-
ditions of the transformer and the
set ∆φ< parameters.
-
273 Limit value ∆φ<< Value has fallen below the limit
value for phase angle difference
∆φ<<.
Check the current operating con-
ditions of the transformer and the
set ∆φ<< parameters.
-
274 Limit value ∆φ> Value has exceeded the limit
value for phase angle difference
∆φ>.
Check the current operating con-
ditions of the transformer and the
set ∆φ> parameters.
-
275 Limit value ∆φ>> Value has exceeded the limit
value for phase angle difference
∆φ>>.
Check the current operating con-
ditions of the transformer and the
set ∆φ>> parameters.
-
276 Protective relay RS of OLTC
column A triggered
The protective relay RS of the on-
load tap-changer (column A) has
triggered.
Contact Maschinenfabrik Rein-
hausen GmbH's Technical Ser-
vice department.
-
277 Protective relay RS of OLTC
column B triggered
The protective relay RS of the on-
load tap-changer (column B) has
triggered.
Contact Maschinenfabrik Rein-
hausen GmbH's Technical Ser-
vice department.
-
278 Protective relay RS of OLTC
column C triggered
The protective relay RS of the on-
load tap-changer (column C) has
triggered.
Contact Maschinenfabrik Rein-
hausen GmbH's Technical Ser-
vice department.
-
279 Pressure relief device of
OLTC column A triggered
The pressure relief device of the
on-load tap-changer (column A)
has triggered.
Contact Maschinenfabrik Rein-
hausen GmbH's Technical Ser-
vice department.
-
280 Pressure relief device of
OLTC column B triggered
The pressure relief device of the
on-load tap-changer (column B)
has triggered.
Contact Maschinenfabrik Rein-
hausen GmbH's Technical Ser-
vice department.
-
281 Pressure relief device of
OLTC column C triggered
The pressure relief device of the
on-load tap-changer (column C)
has triggered.
Contact Maschinenfabrik Rein-
hausen GmbH's Technical Ser-
vice department.
-
282 Pressure relief device of
transformer triggered
The pressure relief device of the
transformer has triggered
Establish the cause of the pres-
sure relief device triggering.
-