5-4
Parameter Name
Default value
V/f control
(Set value: 0)
Vector control
(Set value: 1)
n014 Middle output frequency 1.5 Hz 3.0 Hz
n015 Middle output frequency voltage 12.0 V (24.0 V)
(See note 2.)
11.0 V (22.0 V)
n016 Minimum output frequency 1.5 Hz 1.0 Hz
n017 Minimum output frequency voltage 12.0 V (24.0 V)
(See note 2.)
4.3 V (8.6 V)
n104 Torque compensation primary-delay
time constant
0.3 s 0.2 s
n111 Slip compensation gain 0.0 1.0
n112 Slip compensation primary-delay
time constant
2.0 s 0.2 s
Note 1. Values in parentheses are for 400-V models.
Note 2. For 5.5- and 7.5-kW Inverters, this value is set to 10.0 V for 200-V-class models and to 20.0 V
for 400-V-class models.
Basic Operation
Chapter 5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3MV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3MV SERIES Specifications

General IconGeneral
ModelSYSDRIVE 3G3MV SERIES
CategoryInverter
Input Frequency50/60 Hz
Output Frequency0.1 to 400 Hz
Cooling MethodForced Air Cooling
Input Voltage200 to 240 VAC, 380 to 480 VAC
Horsepower Range0.1 to 15 HP
Power Range0.1 to 11 kW
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationRS-485
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 65°C
Humidity5 to 95% RH (non-condensing)
Vibration5.9 m/s² or less
Voltage Class200V, 400V