EasyManuals Logo

Omron SYSDRIVE 3G3MV SERIES User Manual

Omron SYSDRIVE 3G3MV SERIES
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #114 background imageLoading...
Page #114 background image
5-12
Note 4. Set n149 for the pulse train input scale to the pulse train frequency that is equivalent to the
maximum frequency (FMAX).
The frequency reference set in n004 functions as frequency reference 1 when the Inverter is in multi-
step speed operation. The set values in n025 through n031 and n120 through n127 for frequency ref-
erences 2 through 16 are enabled.
H Selecting the Frequency Reference (n008) in Local Mode
Select the input method of frequency references in local mode.
Two frequency references are available in local mode. Select one of them according to the application.
n008
Frequency Reference Selection in
Local Mode
Register 0108 Hex Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 The settings of the FREQ adjuster in the Digital Operator are enabled. (See note 1.)
1 Key sequences on the Digital Operator are enabled. (See note 2.)
Note 1. The maximum frequency (FMAX) is set when the FREQ adjuster is set to MAX.
Note 2. The frequency reference can be set with key sequences while the FREF indicator is lit or with
the set value in n024 for frequency reference 1. In either case, the value is set in n024.
5-6-2 Upper and Lower Frequency Reference Limits
Regardless of the methods of operation mode and frequency reference input, the upper
and lower frequency reference limits can be set.
H Setting the Upper and Lower Frequency Reference Limits (n033 and
n034)
Set the upper and lower frequency reference limits as percentage based on the maximum frequency
as 100%.
n033
Upper Frequency Reference Limit Register 0121 Hex Changes during
operation
No
Setting
range
0% to 110%
(Max. frequency = 100%)
Unit of
setting
1% Default setting 100
n034
Lower Frequency Reference Limit Register 0122 Hex Changes during
operation
No
Setting
range
0% to 110%
(Max. frequency = 100%)
Unit of
setting
1% Default setting 0
Note If n034 is set to a value less than the minimum output frequency (FMIN), the Inverter will have no
output when a frequency reference less than the minimum output frequency input is ON.
Basic Operation
Chapter 5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3MV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3MV SERIES Specifications

General IconGeneral
ModelSYSDRIVE 3G3MV SERIES
CategoryInverter
Input Frequency50/60 Hz
Output Frequency0.1 to 400 Hz
Cooling MethodForced Air Cooling
Input Voltage200 to 240 VAC, 380 to 480 VAC
Horsepower Range0.1 to 15 HP
Power Range0.1 to 11 kW
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationRS-485
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 65°C
Humidity5 to 95% RH (non-condensing)
Vibration5.9 m/s² or less
Voltage Class200V, 400V

Related product manuals