5-9 Selecting the Stopping Method
This parameter is used to specify the stopping method when the STOP command is
input.
The Inverter either decelerates or coasts to a stop according to the stopping method
selection.
H Selecting the Stopping Method (n005)
n005
Stopping Method Selection Register 0105 Hex Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 Frequency deceleration stop (See notes 1 and 2.)
1 Free running (coasts to stop) (See note 3.)
Note 1. The Inverter will decelerate to stop according to the setting in n020 for deceleration time 1 if
any of the n050 through n056 parameters for multi-function input is not set to 11 for accelera-
tion/deceleration time selection. If any one of the n050 through n056 multi-function input
parameters is set to acceleration/deceleration time selection, the Inverter will decelerate to
stop according to the selected setting of deceleration time when the STOP command is input.
Note 2. If the RUN signal is input again during a deceleration stop, deceleration will be stopped at the
point of the input and operation will accelerate to the frequency reference.
Note 3. Do not input a RUN signal for a free-running stop if the motor’s rotation speed is not sufficient
slowed. If a RUN signal is input under these conditions, a main circuit overvoltage (OV) or
overcurrent (OC) will be detected. To restart a free running motor, set a speed search com-
mand in one of the multi-function inputs 1 to 7 (n50 to n56) and use the speed search to detect
the speed of the free running motor, and then accelerate smoothly.
Basic Operation
Chapter 5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3MV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3MV SERIES Specifications

General IconGeneral
ModelSYSDRIVE 3G3MV SERIES
CategoryInverter
Input Frequency50/60 Hz
Output Frequency0.1 to 400 Hz
Cooling MethodForced Air Cooling
Input Voltage200 to 240 VAC, 380 to 480 VAC
Horsepower Range0.1 to 15 HP
Power Range0.1 to 11 kW
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationRS-485
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 65°C
Humidity5 to 95% RH (non-condensing)
Vibration5.9 m/s² or less
Voltage Class200V, 400V

Related product manuals