EasyManuals Logo

Omron SYSDRIVE 3G3MV SERIES User Manual

Omron SYSDRIVE 3G3MV SERIES
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #195 background imageLoading...
Page #195 background image
7-5
Set Values
When the DSR message is received from the Master, the Inverter must wait for a communications time
of 24-bit length plus the set value in n156 before returning a response.
Set this value according to the response time of the Master.
H RTS Control Selection (n157)
Select whether or not to enable the RTS (request-to-send) communications control function.
This function can be disabled (i.e., set to “1”) only when a 1-to-1 Master/Slave configuration is used in
RS-422 communications. When multiple Slaves are used for RS-422, or whenever RS-485 commu-
nications are used, it is necessary to set “0” (enable RTS control).
n157
RS-422/485 RTS Control Selection Register 019D Hex Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 Enabled
1 Disabled (Available to 1-to-1 RS-422 communication only)
7-1-2 RUN Command Selection (n003)
Select the method to input the RUN or STOP command into the Inverter.
This parameter is enabled in remote mode only. The Inverter in local mode accepts the RUN com-
mand only through key sequences on the Digital Operator.
n003
Operation Command Selection Register 0103 Hex Changes during
operation
No
Setting
range
0 to 3 Unit of
setting
1 Default setting 0
Set Values
Value Description
0 The RUN Key and STOP/RESET Key on the Digital Operator are enabled.
1 Multi-function input terminals are enabled in 2- or 3-wire sequence.
2 RS-422/485 communications are enabled.
3 Input from the option (DeviceNet Communications Unit) is enabled.
Note 1. To input the RUN command through RS-422/485 communications, set this parameter to 2.
Then the RUN command only through RS-422/485 communications will be enabled.
Note 2. The RUN command can be input through RS-422/485 with multi-function input settings as
well. For details, refer to 7-1-4 Setting the Multi-function Inputs.
Communications Chapter 7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3MV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3MV SERIES Specifications

General IconGeneral
ModelSYSDRIVE 3G3MV SERIES
CategoryInverter
Input Frequency50/60 Hz
Output Frequency0.1 to 400 Hz
Cooling MethodForced Air Cooling
Input Voltage200 to 240 VAC, 380 to 480 VAC
Horsepower Range0.1 to 15 HP
Power Range0.1 to 11 kW
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationRS-485
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 65°C
Humidity5 to 95% RH (non-condensing)
Vibration5.9 m/s² or less
Voltage Class200V, 400V

Related product manuals