6-43
Frequency Jump Function
Output
frequency
Reference frequency
6-10-7 Accumulated Operating Time (n087, n088)
• The accumulated operating time function is provided for 5.5- and 7.5-kW Inverters only.
• This function calculates and stores in memory the Inverter’s accumulated operating time. The accu-
mulated operating time that is saved can be checked (unit: 10h) by the “accumulated operating time”
(U-13) of the multi-function monitor (MNTR indicator).
• Use this function in determining the maintenance schedule.
n087
Accumulated Operating Time Register 0157 Hex Changes during
operation
No
Setting
range
0, 1 Unit of
setting
1 Default setting 0
Set Values
• Select the operation status to be accumulated.
Value Description
0 Accumulate the Inverter’s power-ON time (the time from when the power is turned ON until
it is shut OFF).
1 Accumulate the Inverter’s RUN time (the time that the RUN command is being input).
n088
Accumulated Operating Time
Selection
Register 0158 Hex Changes during
operation
No
Setting
range
0 to 6,550 Unit of
setting
10 H Default setting 0
• Set the initial value for the accumulated operating time with 10 hours set as 1. The accumulation will
begin from the time that is set.
Note To clear (i.e., set to 0) the monitor value (U-13) for the accumulated operating time, set n088 to 0.
The monitor value cannot be cleared by setting n001 (parameter write-prohibit selection/parame-
ter initialization) to 8 or 9 (initialize).
Advanced Operation Chapter 6