EasyManuals Logo

Omron SYSDRIVE 3G3MV SERIES User Manual

Omron SYSDRIVE 3G3MV SERIES
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #262 background imageLoading...
Page #262 background image
8-20
H PID control diverges.
No feedback is input.
If the detected value is 0 with no feedback input, the PID control function will not operate. As a result,
the output of the Inverter will diverge and the motor will increase its speed up to the maximum fre-
quency.
Check that the set value in n164 for PID feedback input block selection conforms with the actual
input and that the PID constants are set properly. Refer to 6-3-6 PID Control Settings.
Level adjustments of the target and detected values are imperfect.
The Inverter in PID control adjusts the deviation between the target and detected values so that the
deviation will be zero. Therefore, the target and detected values must be adjusted so that they will
have the same input level. Set the detected value gain in n129 after making the proper level adjust-
ments.
The relationship between the output frequency and detected value of the Inverter is opposite.
PID control will result in diversion if the detected value decreases when the output frequency of the
Inverter increases. If that happens, set n128 for PID control selection to negative characteristics
(e.g., if 1 has been set, change it to 5).
8-2-13 Inverter Vibration in Energy-saving Control
The energy-saving settings are incorrect.
Check the frequency of vibration.
If the frequency coincides with the power averaging time in n143, the Inverter is not in smooth probe
operation. Set the probe operation voltage limit to 0 in n144 to disable the probe operation of the
Inverter or reduce the set values of n145 (100% probe-control voltage step) and n146 (5% probe-
control voltage step) so that the voltage change range will be narrower.
8-2-14 Motor Rotates after Output of Inverter is Turned OFF
Insufficient DC Injection Braking Control
If the motor continues operating at low speed, without completely stopping, and after a deceleration
stop has been executed, it means that the DC injection braking is not decelerating enough.
In such cases, adjust the DC control as described below.
S Increase the parameter in n089 for DC injection braking current.
S Increase the parameter in n090 for DC injection braking-to-stop time.
8-2-15 Detects OV (Over voltage) and Stalls when Motor Starts
Insufficient DC Injection Braking Control at Startup
Generation of OV and stalling can occur if the motor is turning when it is started.
This can be prevented by slowing the rotation of the motor by DC injection braking before starting
the motor.
Increase the parameter in n091 for startup DC injection braking time.
Maintenance Operations Chapter 8

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3MV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3MV SERIES Specifications

General IconGeneral
ModelSYSDRIVE 3G3MV SERIES
CategoryInverter
Input Frequency50/60 Hz
Output Frequency0.1 to 400 Hz
Cooling MethodForced Air Cooling
Input Voltage200 to 240 VAC, 380 to 480 VAC
Horsepower Range0.1 to 15 HP
Power Range0.1 to 11 kW
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationRS-485
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 65°C
Humidity5 to 95% RH (non-condensing)
Vibration5.9 m/s² or less
Voltage Class200V, 400V

Related product manuals