EasyManua.ls Logo

Omron SYSDRIVE 3G3MV SERIES

Omron SYSDRIVE 3G3MV SERIES
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-5
4-2 Operation Example
1 Power Connection
H Checkpoints before Connecting the Power Supply
Check that the power supply is of the correct voltage and that the motor output terminals (R/L1, S/L2,
and T/L3) are connected to the motor correctly.
3G3MV-A2j: Three-phase 200 to 230 V AC
3G3MV-ABj: Single-phase 200 to 240 V AC (Wire R/L1 and S/L2)
3G3MV-A4j: Three-phase 380 to 460 V AC
Make sure that the motor output terminals (U/T1, V/T2, and W/T3) are connected to the motor cor-
rectly.
Ensure that the control circuit terminals and the control device are wired correctly. Make sure that all
control terminals are turned OFF.
Note Set parameter n052 (terminal S3) to 0 if a 3-wire sequence is set.
Set the motor to no-load status (i.e., not connected to the mechanical system).
H Connecting the Power Supply
After conducting the above checks, connect the power supply.
2 Check the Display Status
If the display is normal when the power is connected, it will read as follows:
Normal
RUN indicator: Flashes
ALARM indicator: Off
Simplified-LED (setting/monitor) indicators: FREF, FOUT, or IOUT is lit.
Data display: Displays the corresponding data for the indicator that is lit.
When a fault has occurred, the details of the fault will be displayed. In that case, refer to Chapter 8
Maintenance Operations and take necessary action.
Fault
RUN indicator: Flashes
ALARM indicator: Lit (fault detection) or flashes (alarm detection)
Simplified-LED (setting/monitor) indicators: FREF, FOUT, or IOUT is lit.
Data display: The fault code, such as UV1, is displayed. The display will differ depending on the type
of fault.
Test Run
Chapter 4

Table of Contents

Related product manuals