EasyManuals Logo

Omron SYSDRIVE 3G3MV SERIES User Manual

Omron SYSDRIVE 3G3MV SERIES
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #212 background imageLoading...
Page #212 background image
7-22
Note There is an OR relationship between input from the control terminals and input through commu-
nications. Therefore, if multi-function inputs of this register are set to forward/stop and reverse/
stop, it is possible to execute the RUN command through the multi-function inputs. These settings
are not, however, recommended because these settings establish two command lines.
D Inverter Output (Register 0009 Hex)
Bit No. Function
0 Multi-function contact output (1: ON)
1 Multi-function output 1 (1: ON)
2 Multi-function output 2 (1: ON)
3 to 15 Not used.
Note The settings will be enabled if multi-function outputs 1 through 3 in n057 through n059 are set to
18 for communications output. Then the corresponding output terminal will be turned ON and
OFF through communications.
H Broadcast Message with Slave Address: 00 (00 Hex) Write
Register No.
(Hex)
Function Description
0000 Not used. ---
0001 RUN command Refer to the table below.
0002 Frequency reference Set the frequency reference based on the maximum
frequency as 30,000.
0003 to 000F Not used. ---
Note 1. Data can be written to registers 0001 and 0002 only.
Note 2. No data can be written to multi-function input.
Note 3. The unit of setting of the broadcast message is different from that in the DSR message to com-
municate with a single Slave.
D RUN Command (Register 0001 Hex)
Bit No. Function
0 RUN command (1: RUN)
1 Forward/Reverse (1: Reverse)
2 External fault (1: External fault EF0)
3 Fault reset (1: Fault reset)
4 to 15 Not used.
7-6-2 Monitor Functions
Register No.
(Hex)
Function Description
0020 Status signal Refer to the following corresponding table.
0021 Fault status 1 Refer to the following corresponding table.
0022 Data link status Refer to the following corresponding table.
Communications Chapter 7

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3MV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3MV SERIES Specifications

General IconGeneral
ModelSYSDRIVE 3G3MV SERIES
CategoryInverter
Input Frequency50/60 Hz
Output Frequency0.1 to 400 Hz
Cooling MethodForced Air Cooling
Input Voltage200 to 240 VAC, 380 to 480 VAC
Horsepower Range0.1 to 15 HP
Power Range0.1 to 11 kW
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationRS-485
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 65°C
Humidity5 to 95% RH (non-condensing)
Vibration5.9 m/s² or less
Voltage Class200V, 400V

Related product manuals