7-23
Register No.
(Hex)
DescriptionFunction
0023 Frequency reference According to the set value in n152.
0024 Output frequency According to the set value in n152.
0025 to 0026 Not used. ---
0027 Output current Read based on 1 A as 10.
0028 Output voltage Read based on 1 V as 1.
0029 Fault status 2 (See note.) Refer to the following corresponding table.
002A Warning status (See note.) Refer to the following corresponding table.
002B Input terminal status Refer to the following corresponding table.
002C Inverter status 1 Refer to the following corresponding table.
002D Output terminal status Refer to the following corresponding table.
002E Inverter status 2 (See note.) Refer to the following corresponding table.
002F to 0030 Not used. ---
0031 Main circuit DC voltage Read based on 1 V as 1.
0032 Torque reference Read based on ±1% as ±1 and the rated motor
torque is 100%.
0033 to 0034 Not used. ---
0035 Accumulated operating time
(See note.)
Read based on 1 [h] as 1.
0036 Not used. ---
0037 Output power Read based on ±1 W as ±1. Cannot be monitored in
vector control mode.
0038 PID feedback Read based on 1% as 10 and a value equivalent to
the maximum frequency as 100%.
0039 PID input Read based on ±1% as ±10 and a value equivalent
to the maximum frequency as 100%.
003A PID output Read based on ±1% as ±10 and a value equivalent
to the maximum frequency as 100%.
003B to 003C Not used. ---
003D Communications error Refer to the following corresponding table.
003E to 00FF Not used. ---
Note The fault status 2, warning status, Inverter status 2, and accumulated operating time functions are
provided for 5.5- and 7.5-kW Inverters only.
D Status Signal (Register 0020 Hex)
Bit No. Function
0 During RUN (1: During RUN)
1 Forward/reverse operation (1: Reverse operation)
2 Inverter ready (1: Ready)
3 Fault (1: Fault)
4 Data setting error (1: Error)
5 Multi-function output 1 (1: ON)
6 Multi-function output 2 (1: ON)
7 Multi-function output 3 (1: ON)
8 to 15 Not used.
Communications Chapter 7