5-26
If acceleration/deceleration time selection 2 (setting: 27) is not set at any multi-function input from
n050 to n056, the Inverter will determine that the acceleration/deceleration selection 2 is set to OFF,
and select the acceleration/deceleration time.
In the same way, if acceleration/deceleration time selection 1 (setting: 11) is not set at any multi-func-
tion input, the Inverter will determine that the acceleration/deceleration selection 1 is set to OFF, and
select the acceleration/deceleration time.
Deceleration time 2 is used if emergency stop (setting: 19 to 22) is set at any multi-function input from
n050 to n056 and if decelerate to a stop (setting: 0) is set at stopping mode selection n005.
n019
Acceleration Time 1 Register 0113 Hex Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.) Unit of
setting
0.1 s
(See note
1.)
Default setting 10.0
n020
Deceleration Time 1 Register 0114 Hex Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.) Unit of
setting
0.1 s
(See note
1.)
Default setting 10.0
n021
Acceleration Time 2 Register 0115 Hex Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.) Unit of
setting
0.1 s
(See note
1.)
Default setting 10.0
n022
Deceleration Time 2 Register 0116 Hex Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.) Unit of
setting
0.1 s
(See note
1.)
Default setting 10.0
n041
Acceleration Time 3 Register 0129 Hex Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.) Unit of
setting
0.1 s
(See note
1.)
Default setting 10.0
n042
Deceleration Time 3 Register 012A Hex Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.) Unit of
setting
0.1 s
(See note
1.)
Default setting 10.0
n043
Acceleration Time 4 Register 012B Hex Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.) Unit of
setting
0.1 s
(See note
1.)
Default setting 10.0
n044
Deceleration Time 4 Register 012C Hex Changes during
operation
Yes
Setting
range
0.0 to 6,000 (s) (See note 1.) Unit of
setting
0.1 s
(See note
1.)
Default setting 10.0
Basic Operation
Chapter 5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3MV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3MV SERIES Specifications

General IconGeneral
ModelSYSDRIVE 3G3MV SERIES
CategoryInverter
Input Frequency50/60 Hz
Output Frequency0.1 to 400 Hz
Cooling MethodForced Air Cooling
Input Voltage200 to 240 VAC, 380 to 480 VAC
Horsepower Range0.1 to 15 HP
Power Range0.1 to 11 kW
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationRS-485
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 65°C
Humidity5 to 95% RH (non-condensing)
Vibration5.9 m/s² or less
Voltage Class200V, 400V