EasyManuals Logo

Omron SYSDRIVE 3G3MV SERIES User Manual

Omron SYSDRIVE 3G3MV SERIES
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #162 background imageLoading...
Page #162 background image
6-20
S Measurement of T
Measure the required time (seconds) between the point of intersection of the tangent line and time
axis and the point of intersection of the tangent line and set point line.
Response
Target value
Time
S PID Parameter
The following PID parameters are calculated from the R, L, and T of intersection of the tangent line
and set point line as general rules.
Control Proportional (P) gain
(n130)
Integral (I) time (n131) Derivative (D) time (n132)
P control 0.3/RL --- ---
PI control 0.35/RL 1.2T ---
PID control 0.6/RL T 0.5L
Note 1. Obtain PID parameter values from the above method, set the PID parameters, and tune in the
PID parameter values precisely.
Note 2. PID parameter values obtained from the above method may not be optimum if the friction fac-
tor of the mechanical system is large or the rigidity of the mechanical system is low.
H Manual PID Adjustments
Perform the following procedure to adjust the PID parameter values of the Inverter performing PID
control by monitoring the response waveform.
1. Connect the load in the same way as the connection of the load to the Inverter in normal operation.
2. Set n128 so that the Inverter will perform PID control.
3. Increase the proportional (P) gain in n130 within a range causing no vibration.
4. Increase the integral (I) time in n131 within a range causing no vibration.
5. Increase the derivative (D) time in n132 within a range causing no vibration.
Advanced Operation Chapter 6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3MV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3MV SERIES Specifications

General IconGeneral
ModelSYSDRIVE 3G3MV SERIES
CategoryInverter
Input Frequency50/60 Hz
Output Frequency0.1 to 400 Hz
Cooling MethodForced Air Cooling
Input Voltage200 to 240 VAC, 380 to 480 VAC
Horsepower Range0.1 to 15 HP
Power Range0.1 to 11 kW
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationRS-485
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 65°C
Humidity5 to 95% RH (non-condensing)
Vibration5.9 m/s² or less
Voltage Class200V, 400V

Related product manuals