EasyManua.ls Logo

Omron SYSDRIVE 3G3MV SERIES - Page 170

Omron SYSDRIVE 3G3MV SERIES
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6-28
n093
Stall Prevention Level during
Acceleration
Register 015D Hex Changes during
operation
No
Setting
range
30 to 200 (%) Unit of
setting
1% Set Values 170
Set Values
This function is used to stop accelerating the load if the output current exceeds the set current value so
that the Inverter will continue operating without stalling. The Inverter accelerates the load while the
output current is the same as or less than the set value.
Set the parameter as percentage based on the rated Inverter current as 100%.
The default setting does not need any changes in normal operation.
Decrease the set value if the capacity of the motor is smaller than that of the Inverter or the motor stalls
with the default value.
The set value is normally 2 or 3 times higher than the rated current of the motor. Set this current as
percentage based on the rated inverter current as 100%.
Stall Prevention during Acceleration
Output
current
n093 (stall prevention level
during acceleration)
Time
Output
frequency
The output frequency is controlled
so that the Inverter will not stall.
Time
Advanced Operation Chapter 6

Table of Contents

Related product manuals