9-6
Protec-
i
Motor protection Protection by electronic thermal
tive
func-
tions
Instantaneous
overcurrent
protection
Stops at approx. 250% of rated output current
Overload protection Stops in 1 min at approximately 150% of rated output current
Overvoltage
protection
Stops when main-circuit DC voltage is approximately 820 V
Undervoltage
protection
Stops when main-circuit DC voltage is approximately 400 V
Momentary power
interruption
compensation
(selection)
Stops for 15 ms or more. By setting the Inverter to momentary power
interruption mode, operation can be continued if power is restored within
approximately 0.5 s.
Cooling fin
overheating
Detects at 110 ± 10°C
Grounding
protection
Protection at overcurrent detection level
Charge indicator Charge indicator until main circuit DC voltage reaches 50 V max.
Environ-
Location Indoors (with no corrosive gas, oil spray, or metallic dust)
ment
Ambient operating
temperature
–10 to 50°C Closed
wall-mounting:
–10 to 40°C
Panel-
mounting:
–10 to 50°C
Ambient humidity Operating: 95% max. (with no condensation)
Ambient storage
temperature
–20 to 60°C
Altitude 1,000 m max.
Insulation
resistance
5 MΩ min. (Do not carry out any insulation resistance or withstand
voltage tests)
Vibration resistance 9.8 m/s
2
max. between 10 to 20 Hz
2.0 m/s
2
max. between 20 and 50 Hz
Degree of protection Panel-mounting models: Conforms to IP20 Closed
wall-mounting
(NEMA1)/
Panel- mounting
(IP00)
(See note 3.)
Note 1. The power supply capacity is the capacity for the Inverter’s rated output. It will vary depending
on the impedance at the input power supply. (This is due to fluctuations in the power factor.
The power factor can be improved by inserting an AC reactor.) There will also be variations in
the ratio between the rated current of the motor that is used and the rated output current of the
Inverter.
Note 2. The heat radiation is the electric power consumed in the Inverter at the Inverter’s rated output.
Note 3. The 5.5- and 7.5-kW Inverters are closed wall-mounting models (NEMA1/IP20) as a stan-
dard, but they can be converted to panel-mounting (IP00) by removing the top and bottom
covers.
Specifications
Chapter 9

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3MV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3MV SERIES Specifications

General IconGeneral
ModelSYSDRIVE 3G3MV SERIES
CategoryInverter
Input Frequency50/60 Hz
Output Frequency0.1 to 400 Hz
Cooling MethodForced Air Cooling
Input Voltage200 to 240 VAC, 380 to 480 VAC
Horsepower Range0.1 to 15 HP
Power Range0.1 to 11 kW
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationRS-485
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 65°C
Humidity5 to 95% RH (non-condensing)
Vibration5.9 m/s² or less
Voltage Class200V, 400V