10-28
Param-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of
set-
ting
Set-
ting
range
DescriptionNameRegis-
ter No.
(Hex)
n143 018F Power aver-
aging time
Sets the time required to calculate the
average of power used in energy-sav-
ing control.
Power averaging time (ms) = Set
value x 24 (ms)
* Normally, the default setting does
not need to be changed.
1 to
200
1 (24
ms)
1 No 6-7
n144 0190 Probe opera-
tion voltage
limit
Sets the range of voltage control for
the secondary level of energy-saving
control.
Sets the parameter as a percentage
based on the rated motor voltage as
100%.
* No probe operation is available
with the parameter set to 0.
0 to
100
1% 0 No 6-9
n145 0191 Probe opera-
tion control
voltage step
at 100%
Sets the range of probe operation
voltage as a percentage based on the
rated motor voltage as 100%.
*
Normally, the default setting does
0.1 to
10.0
0.1% 0.5 No 6-9
n146 0192 Probe opera-
tion control
voltage step
at 5%
* Normally
,
the default setting does
not need to be changed.
0.1 to
10.0
0.1% 0.2 No 6-9
n147
--- Not used --- --- --- --- --- ---
n148
n149 0195 Pulse train
input scale
Set this parameter to the pulse train
input scale so that frequency refer-
ences can be executed by pulse train
input.
Set the maximum pulse train fre-
quency in 10-Hz increments based on
10 Hz as 1.
* This parameter is enabled with
n004 for frequency reference
selection set to 5.
100 to
3,300
1 (10
Hz)
2,500 No 5-23
n150 0196 Multi-function
analog out-
put, pulse
train fre-
quency selec-
tion.
Select the relationship between the
pulse train output frequency and out-
put frequency.
0: 1,440 Hz at max. frequency (A pro-
portional relationship is applied to
frequencies less than the maxi-
mum frequency)
1: 1x output frequency
6: 6x output frequency
12: 12x output frequency
24: 24x output frequency
36: 36x output frequency
* This parameter is enabled with
n065 set to 1.
0, 1, 6,
12, 24,
36
1 0 No 5-39
List of Parameters Chapter 10

Table of Contents