3-13
Parame-
ter
Register Name Description Setting
range
Unit of
setting
Default
setting
Chan-
ges dur-
ing
opera-
tion
n001 0101 Parame-
ter write-
prohibit
selec-
tion/pa-
rameter
initializa-
tion
Used to prohibit parameters
to be written, sets parame-
ters, or change the monitor
range of parameters.
Used to initialize parameters
to default settings.
0: Sets or monitor parameter
n001. The parameters within
a range from n002 to n179
can be monitored only.
1: Sets or monitor the
parameters within a range
from n001 to n49 (i.e., func-
tion group 1 settings).
2: Sets or monitor the
parameters within a range
from n001 to n79 (i.e., func-
tion groups 1 and 2 set-
tings).
3: Sets or monitor the
parameters within a range
from n001 to n119 (i.e., func-
tion groups 1 through 3 set-
tings).
4: Sets or monitor the
parameters within a range
from n001 to n179 (i.e., func-
tion groups 1 through 4 set-
tings).
6: Clears the error log.
8: Initializes parameters to
default settings in 2-wire
sequence.
9: Initializes parameters in
3-wire sequence.
10: For the USA, initializes
parameter in 2-wire se-
quence.
11: For the USA, initializes
parameter in 3-wire se-
quence.
0 to 11 1 1 No
Preparing for Operation and Monitoring Chapter 3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3MV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3MV SERIES Specifications

General IconGeneral
ModelSYSDRIVE 3G3MV SERIES
CategoryInverter
Input Frequency50/60 Hz
Output Frequency0.1 to 400 Hz
Cooling MethodForced Air Cooling
Input Voltage200 to 240 VAC, 380 to 480 VAC
Horsepower Range0.1 to 15 HP
Power Range0.1 to 11 kW
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat
CommunicationRS-485
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 65°C
Humidity5 to 95% RH (non-condensing)
Vibration5.9 m/s² or less
Voltage Class200V, 400V